Outline Specifications -- Ecodynamic™ Homes
February 25, 2000

Specification Components
General Requirements/Site/Concrete/Masonry/Metals/Framing/Roofing/Gutters
Exterior Doors/Windows/Siding/Trim/Deck/Porches/Interior Trim/Doors/Cabinets/Insulation
Flooring/Drywall/Paint/Specialty/Appliances/Furnishings/Plumbing/HVAC/Electric

  Specifications created by: Bruce M. Hampton, Architect
    15 Stow Rd. Harvard, MA
    978-456-3733
  1. General Requirements
    The plans, details, and specifications for the project are designed to meet or exceed the requirements of the Massachusetts State Building Code. The Architect must be apprised of any local conditions or requirements which require modifications to the plans, details and specifications. The design criteria for this project are as follows:
      A. Seismic Load: Zone 2
      B. Wind Load: 90 MPH
      C. Live Loads: First Floor: 40 psf Second Floor: 30 psf Roof: Snow 30 psf Attic: 20 psf Exterior Decks 50 psf
    The Owner or Contractor shall be responsible for on site utilities, insurance, telephone, Fax, toilets, materials and methods
    Return to top
  2. Site Work
    All site work is the responsibility of the Owner or General Contractor. This includes all utility connections to within one meter of the foundation or outside wall of the building. Included but not limited to Water Supply, Storm & Sanitary Sewer Lines, all Drainage, Electrical Supply, Telephone, Cable TV, Roads, etc.
    Return to top
  3. Concrete
    All concrete work and engineering is the responsibility of the General Contractor based on local conditions. The Architect shall be responsible for the layout of the foundations, footings, and slabs, based on an assumed allowable soil pressure of 2,000 psf and an assumed concrete strength of 2,500 psi. Dampproofing per plans. Specifications on the engineers plans shall supersede these.
    Return to top
  4. Masonry
    The supply of all masonry materials and engineering shall be the responsibility of the General Contractor. The Architect shall be responsible for the layout of the foundations, footings, and slabs, based on an assumed allowable soil pressure of 2,000 psf. Dampproofing per plans
    Return to top
  5. Metals
    All nails, screws, bolts and other fasteners required for the installation of the building materials are to be included by the Contractor in each section of the work. Any steel reinforcing required for the foundations and footings shall be supplied by the site or foundation contractor.
    Return to top
  6. Framing
      6.1 Sills
    All foundations sills per plans shall be pressure treated; Dow Sill insulation (or equal)shall be used between foundation and sill.
      6.2 Post and Beam Framing Lally Columns
    3-1/2 steel, concrete filled, with steel base and cap Unexposed: Douglas-Fir or micro-lam per plans
      6.3 Floor Framing
    Pre-engineered open web floor joist 19.2" o/c or as per plans, with 3/4" fir T&G plywood for occupied floors. 1/2" CDX ply for unoccupied floors (attics).
      6.4 Exterior Wall Framing
    2x4 or 2x6 @ 16" o/c or as per plans. Surfaced dried SPF #2 or better (or equal) with 7/16" Oriented Strand Board (OSB) sheathing or per plans.
      6.5 Roof Framing
    2x10 Rafters @ 16" o/c or as per plans. Surfaced dried SPF #2 or better (or equal) with 7/16" Oriented Strand Board (OSB) sheathing or per plans. Pre-engineered truss @ 24" o/c or per plans with 5/8" Oriented Strand Board (OSB) sheathing or per plans. Pre-engineered open web floor joist 19.2" o/c or as per plans, with 3/4" fir T&G for flat roofs. Parapet walls per plans
      6.6 Interior Wall Framing
    2x4 framing @ 16" o/c or as per plans. Surfaced dried SPF Stud grade or better (or equal) .
      6.7 Party Wall Framing
    Double 2x3 or 2x4 as required framing @ 16" o/c or as per plans. Surfaced SPF Standard or better (or equal). 1 hour fire-resistive wall between units per local code. Staggered stud w/ continuous 3 1/2" batt insul. between studs. Or double 2x3 stud walls with w/ continuous 3 1/2" batt insulation between studs. Noise transmission: STC 55 or better
    Return to top
  7. Roofing and Gutters
      7.1 Shingles
    Seal down fiberglass mat shingles 235#, 25 year warranty. ( IKO, Bird, GAF or approved equal). 15# felt for underlayment. Aluminum flashing.
      7.2 Eaves
    Continuous eave venting with insect screen, with galvanized drip edge and 50# Bituthane roll roofing as starter strip.
      7.3 Valleys
    50# Bituthane roll roofing or equal
      7.4 Ridge
    Continuous ridge venting with insect screen or per plans.
      7.5 Gutters
    5" aluminum .032 gauge with attachment accessories per plan rectangular downspouts to drywell, storm sewer, or positive drainage per plans.
    Return to top
  8. Exterior Doors and Windows
      8.1 Operable Windows
    Pella Aluminum Clad ProLine with Low-E insulating glass and screen. (per plans) Substitute Pella Designer window where Proline size not available. (same spec)
      8.2 Fixed Glass
    Pella Aluminum Clad Frame with Low-E insulating glass with Argon gas.
      8.3 Roof Glass
    Roto operating skylight with tempered Low-E insulating glass and flashing kit.
      8.4 Exterior Swing Doors
    Morgan Entry Door (M-7100) with lever lock set by Schlage.
    Morgan Sidelights: M-182.
    Accessible lever handle with integral 1" deadbolt. Bright Brass
      8.5 French Door
    Pella Aluminum Clad SmartSash III (without DGP) with Low-E insulated glass and insect screens. Pella traditional French Door lever lock set, bright brass finish.
      8.6 Sliding Glass Door
    Pella Aluminum Clad ProLine with Low-E insulated glass and insect screen.
    Return to top
  9. Siding and Trim
      9.1 Siding
    1/2 x 6 Hardiplank siding (50 year warranty)
    preprimed and painted (15 year warranty)
      9.2 Soffits
    Painted plywood soffit with 2" vent strip.
      9.3 Trim
    Pine #2 and better. Tight sound knots, back primed and finish coat of exterior grade paint. Window pine brickmold per plan.
    Return to top
  10. Decks, Porches, and Steps
      10.1 Balcony Framing
    All framing to be pressure treated. Built up 2x10 beams, 2x8 deck framing.
      10.2 Decking
    5/4 x6 Trex boards
      10.3 Deck Rails/Balusters
    Cedar per plans
      10.4 Deck Steps
    Pressure treated per plans
    Return to top
  11. Interior Doors, Trim, and Stairs
      11.1 Doors
    1 3/8" panel doors by Masonite or equal. Smooth surface finish Coventry or Colonist style. Door hardware to be orbital lock set in bright brass. (Arrow, Schlage or equal) Option: accessible lever handles on all doors where required
      11.2 Interior Trim
    Pine window and door casing (paint grade) 7/16" x 2 1/2" . (5" window sill) Baseboard: 7/16" x 3 1/2" (paint grade) Standard: carpet grade stair per plans
      11.3 Railing standard
    1x pine cap over 2x4 wall w/ painted gypsum wall board graspable 2x6 rail mounted continuously along stair run per plans
    Return to top
  12. Cabinets and tops
      12.1 Kitchen Cabinets
    Merrilat Rutland or equal
      12.2 Countertops
    Plastic laminate : WilsonArt, Plastic laminate or equal. plastic lam. backsplash.
      12.3 Bathroom Vanity Cabinetry
    Merrilat Rutland or equal
      12.4 Bathroom Countertops
    Plastic laminate : WilsonArt, Plastic laminate or equal. plastic lam. backsplash.
    Return to top
  13. Insulation
    Roof: R-38 fiberglass or better. Unfaced batts with continuous air channel.
    Walls: R-19 fiberglass. Unfaced batts with foilbacked sheetrock in exterior walls Foundation wall: 2x4 furring spaced 1" from wall with R-19 batts or per plans
    Crawl space: R-19 batts
    Floors : 6" fiberglass
    Bathrooms: 3-5/8" unfaced batts for sound. 6 mil poly vapor retarder all winter warm surfaces.
    STC ratings: 55 min. dwelling to dwelling and dwelling to common spaces.
    Air tightness: Air leakage ratio of maximum 1.5 square inch per 100 sf of shell area at pressure difference of 4 Pa.
    Return to top
  14. Drywall
      14.1 Gypsum Board
    1/2" gypsum wall board. Ceiling to be smooth finish. Drywall and tape. 5/8" type x gwb per plans. Drywall and tape
      14.2 Backer Board
    Cement based backer board to be supplied for tiled surfaces.
    Return to top
  15. Flooring and Tile
    Living/ /Bedrooms: carpeting: 37# pile weight
    Kitchens/Baths/ Dining/Common Stairs: VCT
    Return to top
  16. Paint and Decorating
      16.1 Interior Walls
    One coat Promar PVA Latex Primer, B28 WC5 One coat EverClean Latex Flat/ Satin to cover
      16.2 Interior Trim and Doors
    One coat ProMar 200 Alkyd Enamel Undercoater B49 W200 Two coats ProMar 200 Alkyd Egg Shell Enamel B33 W201
      16.3 Exterior Siding
    One coat of machine applied primer and one coat of finish. Cabot color selection to be determined.
      16.4 Exterior Trim and all Deck and Railing Trim
    One coat A100 Alkyd Exterior Wood Primer, Y24-W20 One coat Solid Color VOC complying solid color Exterior Stain A14z
    Return to top
  17. Specialties
      17.1 Residential sprinklered for all 3 family buildings as required by local code.
      17.2 3 ft. fencing @ front sidewalk to protect hedgerow.
    Return to top
  18. Appliances
    Energy Star rated appliances:
    Electric range: 30" GE JBP95WW or equal
    Dishwasher: 24" GE GSD 4430 installed at the factory
    Refrigerator: GE model #TBX18Dwhite, top mounted, min.18.2 cu. ft. or equal
    Return to top
  19. Furnishings
     

    19.1 Bathroom accessories

    1. Towel bars, paper holders, etc.,. are white ceramic by Lenape or equal.
    2. Mirror/ Medicine cabinets Bathrooms have recessed, painted white side cabinet to match wall color shutter doors
    3. Mirrors to be maximum size: full width of counter per plans
    4. Shower curtain rod: Lenape or equal

     

    19.2 Closet Shelves

    1. 12 inch wide white wire shelves with coat hanger rod by Shultie or equal.
    2. 16 inch wide white wire pantry and linen shelves by Shultie or equal.

    Return to top
  20. Special Construction

  21. Plumbing (for rough plumbing see plumbing specs)
    distribution: type L copper
    drains, waste, vents: Schedule 40 PVC
    hose bibs in yards (2 min. per building) per plan
     

    21.1 Dwelling Unit Kitchens

    1. Stainless steel sink, Asymmetrical double bowl (one large bowl and one smaller bowl) K-3284 Moen or equal.
    2. Faucet by Kohler K-15173 single lever or approved equal, with sprayer

     

    21.2 Baths

    1. Tub/Shower unit-1 piece white with fiberglass surround
    2. Tub/Shower faucet - Moen "Chateau" L2353, single lever, Chrome
    3. W.C. toilet - Kohler low flow - K3420-K - White
    4. Lavatory - drop in lavatory, White
    5. Lavatory Faucet - Moen L4621 single lever, Chrome.

    Return to top
  22. HVAC
      22.1 Hot Water
    Domestic Hot Water supplied (Polaris or equal gas fired water heater)
    Hydronic baseboard distribution for heating.
    Buildings constructed for annual heating energy input of maximum 1.4 BTU per heating degree day per sf of shell and a cooling input of maximum 2.7 BTU per cooling degree day per sf of shell.
     

    22.2 Ventilation

    1. All bathrooms shall have ventilation fans by Tamarack Technologies, vented directly to exterior.
    2. Range hood by GE or equal vents to exterior .
    3. Ridge, gable, and eave vents per plans

    Return to top
  23. Electric(for rough electric see electrical specifications)
    200 amp service (TBD), 40 position panel and breakers. All wire to be 14 or 12 gauge copper.

     

    23.1 Lighting Fixtures to be selected:

    1. Recessed lighting fixtures in living areas are HALO or approved equal.
    2. Ceiling or Wall fixtures are provided in bathrooms and closets over 3 foot in length.
    3. Exterior lights are provided at each outside door, to be selected

      23.2. Rough Electric
    Contractor to provide all services per plan per local and national electric codes.
      23.3 Security Systems
    Pre-wire for motion detector
     

    23.4 Telephone/Ethernet/Cable

    1. Provide finish telephone service 4 pair twisted wire. 3 locations per unit.
    2. Pre-wire for cable service per plan. 2 locations per unit.

      23.5 Door Chimes
    wire for chimes front door and rear door.
      23.6 Smoke Detectors
    UL approved. Fire alarm systems per code.
      23.7 Outlets and Decora Switches
    White
      23.8 Ground Fault Interrupt circuits for all baths and kitchens per code
      23.9 Exterior Outlets: GFI circuits in waterproof recessed outlets
    . Return to top